High induction CAV & VAV swirl diffuser with fixed horizontal discharge direction, for installation flush with ceiling or free-hanging.
Volume flow range
- 12 – 400 L/s (43 – 1440 m³/h)
Nominal size
- DN200 (square face suitable for 300 mm - 600 mm ceiling grid, or circular face)
- DN250 (square face suitable for 300 mm - 600 mm ceiling grid, or circular face)
- DN350 (square face suitable for 400 mm - 600 mm ceiling grid, or circular face)
- DN500 (square face suitable for 600 mm ceiling grid, or circular face)
Discharge height
Features
- 360° (4-way blow) horizontal discharge pattern.
- Suitable for VAV turning down to approximately 30% @ ∆Tsupply-room ≈ -12 K.
- Neck reducers available to reduce effective neck size to suit reduced airflow rates.
- Segment covers available for 3-way blow (270°) or 2-way blow (2x90° or 180°) patterns.
- Square face standard, circular face optional.
- Optional square perforated screen available to cover face.
- May be freely suspended or located in closed ceiling.